What Cause Diesel Generator Starting Failures?
On this page

Diesel generator starting failures refer to situations where the generator cannot start under normal environmental conditions or specific conditions outlined in the user manual, even after multiple attempts. These failures can disrupt normal operations and may lead to economic losses and safety risks. Below is an in-depth analysis of common starting failures in diesel generators.

Difficulties in Cold Starts


Cold starts in diesel generators pose distinct challenges compared to warm starts. Diagnosing specific symptoms is essential, as they may reveal issues with fuel delivery, combustion efficiency, or engine components. Below are common cold start scenarios, along with their potential causes and solutions.

1. Normal Cranking Speed with No Exhaust Smoke


When a diesel generator starts easily when warm but struggles to start when cold, with normal cranking speed and no exhaust smoke, potential causes are as follows.

Air in the Low-Pressure Fuel Line: If air enters the fuel line during startup, it can create bubbles that prevent diesel from reaching the fuel pump or injectors. It's essential to check the fuel tank seals and line connections, especially if the fuel level is low or if the lines are aging.
Fuel Pump Solenoid Issues: If the solenoid in the fuel pump is not in the supply position, it directly affects fuel delivery, preventing the engine from starting. Regular checks of the solenoid's operational status and power connections are necessary.

2. Normal Cranking Speed with White Smoke from Exhaust


If there is normal cranking speed but white smoke from the exhaust, the issues may include:

Water in the Diesel Fuel: Excessive water content is usually due to improper storage or the use of low-quality diesel. During combustion, this water mixes with the diesel, creating white smoke. It is advisable to use high-quality diesel and regularly clean the fuel tank.
Incomplete Combustion: In cold conditions, diesel may not burn completely, leading to unburned fuel being expelled. Improving combustion efficiency can involve checking and cleaning the injectors to ensure proper atomization.
Coolant Entering the Cylinder: A damaged head gasket or loose cylinder head bolts can allow coolant to seep into the cylinder, hindering proper starting. Regular maintenance checks are essential to prevent such damage.

3. Normal Cranking Speed with Black Smoke from Exhaust


If there is normal cranking speed but black smoke from the exhaust, possible causes include:

Injector Problems: Issues such as leaking or poorly atomizing injectors can cause excessive diesel to enter the cylinder, resulting in incomplete combustion and black smoke. Regular cleaning and calibration of injectors are necessary.

Uneven Fuel Supply: If the fuel pump supplies uneven amounts to different cylinders, it can impair overall engine performance. Regular checks of the fuel pump's operation are recommended to ensure balanced fuel delivery.

Excessive Airflow Resistance: A severely clogged air filter, blocked exhaust pipe, or mismatched muffler can restrict airflow, affecting engine operation. Regularly replacing the air filter and inspecting the exhaust system can help.

Turbocharger Malfunction: A failing turbocharger can reduce airflow to the cylinders, impacting both starting and performance. Ensuring the turbocharger operates correctly is key to enhancing generator performance.

Difficulties in Hot Starts


In some cases, a diesel generator may also struggle to start when hot. This can result from several factors, including the following aspects.

1. Wear in the Fuel Pump Plunger


Worn plungers can increase fuel leakage, reduce pressure, and lower starting performance. Regular inspections and replacing worn components can help prevent this issue.

2. Tight Piston Clearance


If the clearance between the piston and cylinder wall is too tight, it can cause sticking, making it difficult for the engine to start. Regular monitoring and adjustment can alleviate this problem.

3. Overheating of the Generator


High temperatures can degrade lubricating oil, increasing friction during startup. Ensuring the cooling system operates effectively, replacing coolant as needed, and cleaning the radiator can prevent overheating.

4. Insufficient Crankshaft Axial Clearance


If this clearance is too small, it can overload the engine during startup. Regular inspections and necessary adjustments can help maintain optimal conditions.

Difficulties in Both Cold and Hot Starts


Sometimes, a diesel generator may struggle to start whether cold or hot, indicating more complex issues. Potential causes include:

1. Mechanical Wear


Excessive wear between the piston, piston rings, and cylinder can prevent proper combustion of atomized diesel. Regular inspections and timely replacements of worn parts can resolve this issue.

2. Poor Piston and Cylinder Ring Alignment


Misalignment can impact combustion efficiency and make starting difficult. Checking and adjusting the fit is necessary.

3. Valve Clearance Issues


Worn valves may have excessive clearance or too little clearance, both of which can affect cylinder pressure and make diesel ignition difficult. Regular checks of valve clearance can enhance startup performance.

4. Poor Injector Performance


Clogged injectors can lead to insufficient fuel delivery, directly impacting starting. Cleaning and checking injectors regularly ensures proper function.

5. Improper Fuel Pump Governor Adjustment


If the governor isn't properly calibrated, it can result in inadequate fuel delivery, affecting startup. Regular calibration of the fuel pump is necessary for optimal performance.

6. Low-Pressure Fuel Line Issues


Problems in the low-pressure line can also prevent diesel from reaching the injectors, hindering startup. Check all connections for leaks and ensure the lines are clear.

Conclusion


The causes of diesel generator starting failures are complex and varied, involving fuel systems, mechanical wear, and cylinder sealing issues. Identifying specific problems requires thorough inspection and maintenance to ensure proper generator operation. Regular upkeep, attention to fuel quality, and monitoring environmental conditions can effectively prevent starting failures, improving the generator's efficiency and reliability. Proper operation and maintenance not only extend the generator's lifespan but also reduce repair costs, ensuring smooth production processes.

 