Preheating Process for Diesel Generators in Cold Conditions
On this page
 
The start-up process of diesel generator sets is particularly complex in low-temperature environments, especially when the temperature drops below 10°C. The engine may encounter difficulties starting in such conditions. To ensure smooth startup and maintain normal operation, the preheating system plays a crucial role. By using the preheater to warm the intake air and increase the compression temperature inside the cylinders, the ignition of the fuel is assisted, preventing startup failures or delays. This article provides a detailed guide on the preheating operation steps for diesel generator sets and highlights key details to pay attention to during the startup process to help optimize performance and extend the equipment's lifespan.

Components and Functions of the Preheating System

 
The preheating system of a diesel generator set consists of a hand fuel pump, glow plug, and associated circuits. The hand fuel pump is responsible for pumping fuel into the intake manifold, while the glow plug, powered by the battery, heats the fuel. The fuel burns in the intake manifold, further heating the incoming air to a temperature that supports effective fuel ignition. It's important to note that the preheater should not be used simultaneously with steam equipment used to assist the startup, as this may cause a fire and increase safety risks during the startup process.

Detailed Preheating Process

 
The preheating operation for diesel generator sets must follow a strict sequence to ensure smooth startup in cold conditions.
 
Set Throttle to Idle Position: Begin by setting the throttle to the idle position to ensure the engine starts under a light load, which helps it warm up gradually.
 
Turn On the Glow Plug Switch: Set the glow plug switch to the "ON" position. The red indicator light should turn on, indicating that the preheating process has begun.
 
Wait 20 Seconds: After the red indicator light turns on, wait for about 20 seconds to allow the glow plug to fully heat the air in the intake manifold.
 
Start the Diesel Generator: After 20 seconds, start the diesel generator while operating the hand fuel pump to maintain fuel pressure. Be cautious not to use the hand fuel pump too early, as it may wet the glow plug with fuel, reducing its heating efficiency and leading to startup failure.
 
Control the Start Time: If the engine does not start within 30 seconds, stop the operation immediately and wait 1-2 minutes before trying again. This interval helps prevent excessive battery discharge and overheating of the starter motor.
 
Idle Operation and Hand Fuel Pump Use: In cold weather, the engine should idle for 4-5 minutes to warm up fully. During this time, the hand fuel pump should be operated slowly to ensure stable fuel pressure. When the engine reaches working temperature and the hand fuel pump no longer vibrates significantly, stop using the pump.
 
Turn Off the Glow Plug: Once the engine stabilizes at idle, turn off the glow plug switch. The indicator light will go off, indicating that the preheating process is complete.

Common Preheating Issues and Solutions

 
If the diesel generator set shows no sign of starting after three preheater operations, check the temperature of the intake manifold. If the intake manifold is not warm, it may indicate a circuit failure, and troubleshooting is needed. The specific steps are as follows.
 
Remove the 3.2mm plug near the glow plug on the intake manifold.
Manually turn on the glow plug switch for about 15 seconds and observe whether the glow plug reaches a white-hot state.
If the glow plug does not turn white-hot, it may be due to insufficient current. The current should be measured to ensure it falls between 30-32A.
If the glow plug is functioning normally, proceed to check the manual switch and resistance and replace them if necessary.

Diesel Generator Startup Process

 
With the preheating system functioning correctly, the startup process for diesel generator sets must follow precise steps to ensure smooth operation and prolong the equipment's lifespan.

1. Determine if Preheating is Necessary

 
Based on the ambient temperature, decide whether to use the preheating system. Preheating is especially important in low temperatures (below 10°C). Use the preheat button on the control panel to activate the glow plug and heat the air inside the cylinders to aid fuel ignition.

2. Activate the Control Panel and Check Status

 
Turn the key switch on the control panel to the "ON" position and confirm that the background lights on the dashboard are lit, indicating that the fuel system and electronic governor are operational.

3. Select Startup Mode

 
Some generator sets have an idle/full-speed switch. Idle startup is used for gradual warming and should typically last no more than five minutes. Full-speed startup is used for quicker operation.

4. Press the Start Button

 
Press the start button, keeping the startup time within 30 seconds. If the generator successfully starts, release the button, and the generator enters normal operation. If unsuccessful, wait 1-2 minutes before trying again.

5. Control Startup Duration and Interval

 
To extend the life of the starter battery and motor, it is recommended to limit each startup attempt to 5-10 seconds. If unsuccessful, pause before trying again to avoid prolonged startup attempts.

6. Enter Operating Mode

 
After successful startup, the generator enters normal operation. The operator should monitor oil pressure, temperature, and RPM to ensure all parameters are normal and promptly address any abnormalities.
 
This process ensures that the diesel generator set starts smoothly, especially in low temperatures or special conditions, guaranteeing stable operation of the equipment.

Conclusion

 
The preheating process of diesel generator sets is a critical step in ensuring reliable startup in low-temperature conditions. By using the glow plug system to heat the intake air, the diesel engine can ignite smoothly. Following the preheating and startup steps carefully helps extend the lifespan of the diesel generator set and prevents failures or safety hazards caused by improper operation. In extreme weather conditions, proper use of the preheater is particularly important to ensure the generator set remains efficient and operational.

 
Share this post


Nickname*:
E-mail*:
Rate*:
Comments*:

About the author
Issac
Issac
Related News