How to Fix Low Charging Current in Diesel Generators
On this page

Diesel generators are crucial backup power sources, but just like any equipment, they can run into problems over time. One common issue you might encounter is low charging current, which affects the generator's ability to charge its battery and can disrupt the whole system. In this article, we'll dive into what causes low charging current in diesel generators and how you can troubleshoot and fix it.

What Causes Low Charging Current?


There are a few different reasons why a diesel generator might have low charging current. Let's take a look at the most common ones.

1. Belt Slippage


If the belt driving the generator slips, the generator can't reach the right speed. This means it won't produce enough current, which leads to low charging. This could be due to issues like loose or worn-out belts, or even the wrong material for the belt.

2. Voltage Regulator Problems


The voltage regulator controls the excitation current that adjusts the generator's output voltage. If the regulator isn't working properly or its settings are too low, the generator might not charge the battery as it should. The regulator does this by controlling the excitation current through a shunt.

3. Grounding or Short Circuit in the Magnetic Field Coil


If the magnetic field lines in the generator are grounded or if there's a short circuit in the coil, the excitation circuit fails. Without the right excitation current, the generator can't produce enough power, which affects the charging current.

4. Damaged Silicon Diodes or Loose Wires


Most diesel generators have a rectifier system made up of silicon diodes. If these diodes are damaged or if the wires come loose, it can break the electrical connection in the armature winding, which stops the generator from charging properly, causing low charging current.

5. Poor Contact Between Brushes and Slip Rings


Another reason for low charging current could be poor contact between the brushes and slip rings. Dirt buildup on the slip rings, worn-out brushes, or weak spring pressure can all increase contact resistance. This reduces the excitation current, which leads to low charging current.

How to Troubleshoot Low Charging Current


If you're facing low charging current, follow these steps to troubleshoot the issue.

1. Check the Belt


Start by inspecting the belt. Is it slipping or too loose? A loose or slipping belt won't let the generator reach the correct speed, which affects the charging current. Adjust the belt tension to ensure it's tight enough to work properly.

2. Test the Voltage Regulator


The voltage regulator controls the excitation current and the generator's output voltage. If it's malfunctioning, check its settings. Use a multimeter to measure the output voltage and see if it's within the normal range. If it's too low, the regulator might need to be repaired or replaced.

3. Check the Magnetic Field Coil and Grounding


Use a multimeter to measure the resistance between the magnetic field terminal and the grounding terminal. You should get a resistance value within the normal range. If the resistance is too low or zero, it could mean there's a short circuit in the magnetic field coil, and you'll need to fix it.

4. Test the Silicon Diodes


Check the silicon diodes using a multimeter. If you find any damaged or burned-out diodes, replace them and re-solder the leads to restore the charging circuit.

5. Inspect the Brushes and Slip Rings


Look at the brushes and slip rings to make sure they're in good condition. Check for dirt buildup on the slip rings or excessive wear on the brushes. Also, make sure the spring pressure is sufficient. If needed, clean the slip rings, replace the brushes, or adjust the spring pressure to ensure a solid connection.

6. Measure the Charging Current and Output Voltage


Once the generator is running, use the current meter and multimeter to measure the charging current and output voltage. If the charging current is still low, check the output voltage. If it's below the normal range, it could be a sign of an internal electrical fault. You may need to check the internal components for problems.

How to Fix the Problem


Once you've figured out the cause, here's how to fix the issue.

Adjust the Belt Tension: If the belt is slipping or too loose, adjust its tension. A properly tightened belt will help the generator reach the right speed and produce enough current for proper charging.

Replace or Repair the Voltage Regulator: If the voltage regulator is faulty, replace or repair it. Make sure it's set up correctly to control the excitation current and ensure the generator's output voltage is at the right level.

Fix the Magnetic Field Coil Issue: If the magnetic field coil is grounded or short-circuited, you'll need to disassemble the generator and repair or replace the damaged coil parts to restore proper excitation.

Replace Damaged Silicon Diodes: If you've found that the silicon diodes are damaged, replace them and re-solder the leads to ensure the charging circuit is intact.

Clean the Slip Rings or Replace the Brushes: If the brushes and slip rings are having trouble making contact, clean the slip rings and replace the worn-out brushes. You might also need to adjust the spring pressure to make sure the connection is strong.

Adjust the Voltage Regulator Settings: If the voltage regulator's settings are too low, you can adjust them to ensure they're within the proper range to meet the generator's needs.

Verify the Fix


After you've made the repairs, restart the generator. Keep an eye on the charging current meter to check if the current has returned to normal. Run the generator at 1300 RPM and measure the charging current. If the current hits 15A, then the generator is back to normal, and the charging system is working properly.

Conclusion


Low charging current in diesel generators can be caused by a number of issues, like a slipping belt, voltage regulator malfunction, magnetic field coil problems, damaged silicon diodes, or poor contact between brushes and slip rings. By following a simple troubleshooting process and fixing the root cause, you can get the generator back in action. Regular checks and maintenance are key to preventing these issues and keeping your generator running efficiently for a long time.
 