Troubleshooting Diesel Generators Failing to Auto-Shutdown
On this page
 
Diesel generator sets are crucial backup power systems widely used in industrial, commercial, and public facilities. However, during operation, these diesel generators may sometimes fail to shut down automatically, affecting their normal function and safety. This article provides a detailed analysis of the main causes of such failures and offers troubleshooting methods and preventive measures to help users enhance the reliability and operational efficiency of their equipment.

Causes of Diesel Generators Failing to Auto-Shutdown

 
Automatic shutdown failure in diesel generator sets is a common yet complex issue. It can arise from various factors, including electrical component failures, control system anomalies, and operational errors.

1. Shutdown Relay Failure

 
The shutdown relay is a critical component that controls the shutdown of the diesel engine. If the relay malfunctions, the engine will not shut down properly. Common causes include:
Voltage Issues: Measure the operating voltage of the shutdown relay using a multimeter and compare the reading with the normal value. If the voltage is normal but the relay does not actuate, the issue may be internal relay failure.
Relay Damage: If the relay has a normal voltage but no action, it could indicate a damaged coil or contact points, necessitating a replacement.

2. Shutdown Solenoid Valve Failure

 
The shutdown solenoid valve cuts off fuel supply to stop the engine. If it fails, the engine will continue to idle as fuel supply is not properly halted. Possible causes and solutions include:
Voltage or Blockage Issues: Use a multimeter to check the solenoid valve's operating voltage and resistance. If the valve is dirty or blocked, disconnect its power supply, dismantle it for cleaning, and adjust the tension of the solenoid spring to ensure proper closure.
Control Circuit Faults: If the problem persists after cleaning, check the control circuit for incorrect wiring or short circuits. Replace the solenoid valve if necessary.

3. Governor Malfunction

 
The governor regulates the engine's speed and load. A malfunctioning governor can prevent the engine from shutting down properly. Common scenarios include:
Governor Out of Control: If the governor is out of control, the engine speed cannot be reduced to a shutdown state. Professional inspection and repair are required.
Sensitivity Issues: The governor's sensitivity may be affected by mechanical wear or improper adjustments, preventing proper shutdown. Adjustment or replacement of the governor is necessary.

4. Control System Operational Errors

 
Incorrect operational procedures during generator shutdown can also cause failure. For example:
Incorrect Shutdown Sequence: If the control panel key switch is turned off before pressing the shutdown button, the shutdown will fail. The correct sequence is to press the shutdown button first to stop the unit, then turn off the key switch.

5. ATS (Automatic Transfer Switch) Signal Anomalies

 
ATS is primarily used for automatic power source switching. If the ATS shutdown signal is not transmitted correctly, the generator may continue to run. Solutions include:
Cooling Shutdown: If the ATS signal is cut off but the unit continues to run, it may be in a cooling mode, allowing the unit to shut down automatically after a period.

Diesel Generator Shutdown Methods

 
Diesel generators typically use two shutdown methods: fixed parameter shutdown and sliding parameter shutdown, each suitable for different scenarios.

1. Fixed Parameter Shutdown

 
Fixed parameter shutdown maintains constant main steam parameters while reducing the load by adjusting the steam intake. This method is ideal for situations requiring quick load recovery.
Process: During shutdown, keep the main steam parameters constant, and reduce steam intake through the throttle valve. The load can generally be reduced to zero within 40-50 minutes, followed by electrical disconnection and turbine shutdown.
Advantages: The turbine metal temperature remains high after shutdown, facilitating rapid load recovery during restart.
Precautions: Control the rate of metal temperature decrease during load reduction to avoid rapid temperature changes that could damage equipment. The recommended rate is within 1.5°C per minute.

2. Sliding Parameter Shutdown

 
Sliding parameter shutdown gradually reduces load by lowering main steam parameters while keeping the throttle valve fully open, allowing the cylinder temperature to decrease to a lower level, making maintenance easier.
Process: Reduce the load to 80-85% of the rated value, keep the throttle valve fully open, and lower the main steam parameters. As the metal temperature decreases and the component temperature differences reduce, gradually reduce the load to zero, followed by boiler shutdown and generator disconnection.
Advantages: The temperature drops to a lower level post-shutdown, facilitating equipment maintenance and shortening downtime.
Applications: Suitable for large units above 20MW, usually adopting sliding parameter shutdown.

3. Preventive Measures and Recommendations

 
To prevent automatic shutdown failures in diesel generator sets, the following measures should be taken:
Regular Inspection and Maintenance: Periodically inspect and maintain key components such as the shutdown relay, solenoid valve, and governor to ensure they are in good condition.
Standardized Operating Procedures: Ensure that operators are familiar with the shutdown procedures and follow the correct sequence to avoid shutdown failures caused by operational errors.
Enhanced Monitoring and Alarms: Equip diesel generator sets with monitoring and alarm systems to monitor operating status in real-time and promptly address any anomalies.
Training and Emergency Drills: Regularly train operators to improve their ability to identify and handle generator faults. Conduct emergency drills to enhance response capabilities.

Conclusion

 
In summary, automatic shutdown failures in diesel generator sets are primarily caused by electrical component issues, operational errors, and equipment performance problems. Regular inspection and maintenance of key components such as shutdown relays, solenoid valves, and governors can significantly reduce the occurrence of such faults. Additionally, standardized operating procedures and effective monitoring methods are essential for ensuring the safe operation of generator sets. It is hoped that the analysis and recommendations provided in this article can serve as a reference for the management and maintenance of diesel generator sets, ensuring their stable and reliable performance in critical situations.
 
 