Preventing High-Temperature Alarms in Diesel Generators
On this page
 
Diesel generators often encounter high-temperature alarm faults, particularly in summer or high-temperature environments. If these issues are not promptly addressed, they can lead to severe mechanical damage, such as cylinder scoring, cylinder head failure, power reduction, decreased oil viscosity, increased friction between components, or even equipment failure. Therefore, understanding the causes of high-temperature alarms and implementing preventive measures is crucial for ensuring the stable operation and extending the lifespan of diesel generators. This article explores the causes and preventive measures for high-temperature alarms to help users maintain the proper functioning of their diesel generators.

Common Causes of High-Temperature Alarms in Diesel Generators

 
High-temperature alarms are a common and significant issue during the operation of diesel generators. Identifying the causes not only helps in timely fault resolution but also prevents similar issues in the future. Here are some common causes of high-temperature alarms

1. Extended Overload Operation

 
Operating a diesel generator under high load for extended periods increases fuel consumption and thermal load, leading to excessive coolant temperatures. Prolonged high-temperature operation not only affects engine performance but also accelerates component wear. Users should avoid overloading the generator and regularly monitor its load to ensure it operates within its rated capacity.

2. Insufficient Coolant

 
Insufficient coolant is a frequent cause of high-temperature alarms. The coolant in the cooling system effectively removes the heat generated during engine operation. A shortage of coolant significantly reduces cooling efficiency, causing high temperatures in the generator. Users should regularly check the coolant levels in the radiator and expansion tank and replenish them as needed. Reliance on low-level alarms alone is not advisable, as these sensors can sometimes malfunction due to blockage in small pipes.

3. Blocked Radiator

 
A blocked radiator is another common cause of high-temperature alarms. Dust, dirt, or other debris on the radiator's surface can obstruct airflow and reduce cooling efficiency. Additionally, bent or broken radiator fins can restrict airflow. Users should regularly clean the radiator surface and use high-pressure air or water carefully to avoid damaging the fins, especially the intercooler fins.

4. Aging or Scaling of the Cooler

 
Over time, coolers can accumulate compounds that impair heat exchange efficiency, leading to high water temperatures. Users can use a temperature gun to measure the temperature difference between the cooler's inlet and outlet to assess its performance. If necessary, clean or replace the cooler according to manufacturer recommendations to ensure optimal cooling performance.

Preventive Measures for High-Temperature Alarms

 
To ensure the normal operation of diesel generators and effectively prevent high-temperature alarms, users should adopt a series of preventive measures. Here are some key steps and recommendations to help maintain equipment within safe temperature ranges.

1. Regularly Check Coolant Levels

 
Coolant is essential for the heat dissipation of diesel generators. Regularly check the coolant levels in the radiator and expansion tank, and replenish as needed based on operational conditions. After a high-temperature shutdown, wait for the coolant temperature to return to a safe range before adding more coolant to prevent damage to the cylinder head or cylinder block.

2. Keep the Radiator Clean

 
Dust and dirt on the radiator surface can obstruct airflow and reduce cooling efficiency. Regularly inspect the radiator and clean it using high-pressure air or water. During cleaning, avoid bending the radiator fins to maintain proper airflow. If the radiator is deformed or damaged, repair or replace it promptly.

3. Inspect the Air Cooling System

 
For air-cooled diesel generators, users should regularly check the integrity of the airflow guide plates and shields. Damaged shields may cause hot air to flow back into the intake, affecting cooling performance. The outlet area should be 1.1 to 1.2 times the area of the cooler to ensure good airflow. When installing fan shields, ensure the fan's airflow direction and shield installation are correct to maintain cooling efficiency.

4. Check the Fan Belt and Fan Condition

 
A loose fan belt can reduce fan speed, affecting the radiator's cooling efficiency and increasing generator temperature. Regularly check and adjust the fan belt tension. A belt that is too loose affects fan speed, while one that is too tight increases wear on the belt and bearings, reducing their lifespan. Additionally, inspect the fan for deformation, which can impact cooling performance.

5. Inspect the Thermostat and Water Pump

 
A faulty thermostat can prevent the cooling system from regulating temperature properly, leading to high-temperature alarms. Use a temperature gun to measure the temperature difference between the water tank inlet and water pump inlet to assess thermostat functionality. If the thermostat is defective, remove it for further inspection and measure its opening and full-open temperatures. Additionally, regularly check the water pump for scale buildup that could affect cooling efficiency.

6. Maintain the Hydraulic System

 
In some diesel generators, the hydraulic oil cooler is positioned before or after the water cooler. Excessive hydraulic oil temperature can affect the inlet temperature of the water cooler, reducing cooling effectiveness. Regularly inspect and maintain the hydraulic system to ensure the hydraulic oil cooler functions properly, preventing impacts on the water cooling system.

Additional Maintenance Recommendations

 
In addition to preventive measures for high-temperature alarms, regular maintenance of diesel generators is crucial. Comprehensive and detailed maintenance helps ensure the generator operates reliably and efficiently over the long term. Here are some additional maintenance suggestions.

1. Avoid Using Low-Quality Coolants

 
Low-quality coolant can lead to scale formation, impairing radiator efficiency. Choose high-quality coolants to minimize scale buildup and ensure efficient cooling system operation.

2. Proper Radiator Layout Design

 
When designing diesel generators, arrange the radiators to avoid interference between hydraulic oil coolers and water coolers. If they are placed together, implement appropriate isolation measures to prevent heat transfer between them.

3. Regular Maintenance and Service

 
Regular maintenance is critical for diesel generators. Develop a detailed maintenance plan based on the generator's usage frequency and operating environment. Regularly check all systems, identify potential issues early, and address them promptly.

Conclusion

 
High-temperature alarms in diesel generators are a common issue, especially during hot summer months. By understanding the causes and implementing preventive measures, users can effectively avoid damage caused by overheating. Regularly checking coolant levels, cleaning the radiator, ensuring the proper operation of the air cooling system and fan, and maintaining the hydraulic system and thermostat are key steps in maintaining diesel generator performance. Proper regular maintenance helps prevent equipment failure due to negligence and ensures the generator operates safely and reliably.

 
 
 
Share this post


Name*
E-mail*
Rate*
Comments*

About the author
Issac
Issac
Related News