Diesel Generator Shutdown Procedures: Normal vs. Emergency
On this page

Properly shutting down a diesel generator is really important after it's been running normally. It helps protect the equipment, extend its lifespan, and minimize the chances of potential damage or failures. A shutdown isn't just about maintenance; it also involves checking the system after power comes back, troubleshooting issues, and taking safety precautions. In this article, we'll break down the normal shutdown process of diesel generators, how to handle emergency shutdowns, and important things to keep in mind to ensure everything runs smoothly, no matter the situation.

Normal Shutdown Procedures

 

Shutting down a diesel generator should be done in a specific order to ensure a smooth transition after power loss and avoid any damage from sudden temperature or load changes. Here's a simple breakdown of the normal shutdown process.

1. Unload the Load and Turn Off the Power Switch

 

Before you start shutting down, first, remove the load and turn the generator's power output switch to the "OFF" position. This step helps prevent the shock of suddenly disconnecting the load, which could affect the stability of the generator's internal components.

2. Gradually Reduce Engine Speed

 

After unloading the load, the engine speed should be slowly reduced. For low-speed diesel generators, aim for around 160–200 rpm. For high-speed generators, bring it down to around 600–700 rpm. This step reduces strain on the engine and helps cool the turbocharger, preventing it from overheating and damaging the bearings.

3. Run Idle for 3 to 5 Minutes

 

After lowering the speed, let the diesel generator run idle for 3 to 5 minutes. This gives the engine components, especially the turbocharger, a chance to cool down. This helps avoid any damage caused by high temperatures when the generator shuts off suddenly. The turbocharger continues running during this time to release any built-up heat.

4. Ensure Cooling Temperature is Safe

 

Before you shut down completely, make sure the cooling water temperature drops below 75°C. This prevents the engine from overheating, which could damage the internal parts. If the cooling water is too hot, shutting down could cause the engine temperature to rise quickly, which can cause even more damage. So, wait for the temperature to drop to a safe level before starting the shutdown process.

5. Special Handling for Freezing Temps (Below 0°C)

 

When the outside temperature is below 0°C, it's crucial to drain the cooling water after the shutdown to avoid frozen pipes or other freeze-related damage. However, this doesn't apply if the generator uses antifreeze, as antifreeze prevents freezing. A couple of things to note:

Don't drain the water right after shutting down. Wait for the cooling water to cool to about 40°C to avoid overheating the engine block, which could damage parts.

It's generally a good idea to wait around 30 minutes after shutting down before draining the water.

6. Maintenance for Long-Term Shutdown

 

If the generator is going to be out of service for a long period, make sure you take extra care when shutting it down for storage. It's a good idea to drain the engine oil and replace it with preservation oil, running the engine for about 2 minutes to ensure proper preservation. Also, drain the cooling water and antifreeze, and take care of the battery (like removing it and storing it properly).

Emergency Shutdown Handling

 

If the generator experiences an emergency failure or if it's not possible to shut it down normally, you should immediately follow emergency shutdown procedures. Emergency shutdown is needed in situations like:

1. Low or No Oil Pressure

 

If the generator's oil pressure drops quickly or disappears, it can cause the engine to lose lubrication, leading to serious damage. If this happens, shut down the generator right away and check the oil system.

2. Electrical System Failure

 

If there's an issue with the electrical system or the automatic control system, or if the voltage or current exceeds the maximum reading and can't be adjusted, shut the generator down immediately. This helps prevent more damage caused by electrical issues.

3. Engine Over-Speed (Runaway)

 

If the generator experiences over-speed (where the engine speed goes out of control and rises rapidly), it's usually because of a throttle system failure or other mechanical issues. In this case, emergency shutdown measures should be taken immediately, as over-speed can severely damage the engine. This may involve blocking the air intake or cutting off the high-pressure fuel line to stop the engine.

4. Abnormal Noise or Vibration

 

If the generator makes strange knocking sounds or experiences excessive vibration, it could indicate serious internal problems or loose parts. Shut it down right away and check the mechanical condition of the equipment.

5. Emergency Incidents or Natural Disasters

 

If there's a fire, electrical leak, or any situation that threatens safety, or if there's a natural disaster like an earthquake or flood, take immediate emergency shutdown actions to protect both people and equipment.

Emergency Shutdown Steps

 

In an emergency situation, the steps should be quick and straightforward to ensure a fast and effective response.

Cut the Power and Remove the Load: First, immediately cut the power circuit and remove the load to prevent further damage to the electrical equipment.

Turn Off the Fuel Supply: Quickly push the fuel shutoff lever to the "off" position to stop the fuel supply.

Block Air Intake or Cut Off High-Pressure Fuel Line: If over-speed occurs, immediately block the air intake or cut off the high-pressure fuel line to force the engine to stop.

Conclusion

 

Proper shutdown procedures are crucial for keeping diesel generators running smoothly in the long term. Following the right steps helps prevent damage and extends the equipment's lifespan. In the event of sudden failures, emergency shutdown actions are key to protecting both the equipment and the people around it. Maintenance teams should adjust the shutdown process based on the specific situation to ensure the generator stops safely and smoothly. Regular monitoring and timely troubleshooting can prevent secondary damage or accidents caused by improper shutdown.